ULTRASTAT-SC
ELECTRICAL PROPERTIES:
PTP: 2.5 x 104 to 106 per NFPA-99 @ 500 V
RTG: 2.5 x 104 to 106 per EOS / ESD S7.1
STATIC DECAY:
Conditioning: 50% RH +/-2%@23° C+/-1° for 24 Hours
Test conducted @: 50% RH+/-2%@23° C+/-1° C
Test results=Time, seconds to decay to 10% of initial charge
Results, <0.01 seconds
ULTRASTAT-SD
ELECTRICAL PROPERTIES:
PTP: 2.5 x 106 to 108 per NFPA-99 @ 500 V
RTG: 2.5 x 106 to 108 per EOS / ESD S7.1
STATIC DECAY:
Conditioning: 50% RH +/-2%@23° C+/-1° for 24 Hours
Test conducted @: 50% RH+/-2%@23° C+/-1° C
Test results=Time, seconds to decay to 10% of initial charge
Results, <0.02 seconds
OTHER PROPERTIES:
ASTM F 1700 |
Passes |
Underwriters Laboratories |
Meets UL Standard |
NFPA Life Safety Code 101 |
Class I Interior Floor Finish |
Critical Radiant Flux (ASTM E 648) |
Ultrastat-SC >1.08 W / cm2
Ultrastat-SD >1.03 W / cm2 |
Smoke Density Test (ASTM E 662) |
<450 |
Flame Spread (ASTM E 84) |
<75 |
Static Load Limit
(Modified ASTM F 970-93) |
2,500 psi |
CONSTRUCTION
Composition: |
Homogeneous solid vinyl tile that has encapsulated conductive elements of the carbon family distributed throughout the tile. |
Gauge: |
1/8" |
Nominal Sizes: |
12" x 12" and 36" x 36" |
Custom Sizes Available: |
24" x 24" available in selected colors only. |
|
|
INSTALLATION |
|
Adhesive & Spread Rate: |
#150 Conductive Epoxy Adhesive; Covers 150 square feet / gallon. |
Trowel Size:* |
Type one: 1/16"x1/16" Square Notch with 1/16" Flats
Type two: 1/16"x1/16" Half Circular Notch with 1/32" Flats |
Grounding: |
One 2"x 24" copper strip installed every 2,000-2,500 feet. |
Trowel size is dependent upon tile size, surface type and condition, Please refer to installation instructions for proper trowel size selection. |
|